Brunnen SH0851bH

Good to know Data & facts

Connection size

DN 15 to DN 50 1/2" to 2"

Set pressure

0.5 bar to 25 bar

Temperature

-10 °C to 120 °C
Product design

angle-type

Material

Gunmetal

Nominal width

DN 15 to DN 50
1/2″ to 2″

Medium
  • Hot water
Temperature in °C

-10 °C to 120 °C

Pressure in bar

0.5 bar to 25 bar

High performance safety valve with bellows, made of high quality, corrosion-resistant gunmetal. Heating systems with set pressures other than 2,5 or 3 bar are required to be protected by such safety valves. Apart from indirectly heated plants, the sizing of the valves is based on the heating output of the boiler.


connection types

  • Internal pipe thread
  • Male thread

Application

  • CHP units (combined heat and power plants)
  • biogas plants
  • District heating transfer stations/ house stations
  • Solar systems
  • closed, thermostatically protected water heating systems

In the event of failure of the thermostatic control and limiting devices, the safety valve must blow off the entire heating output of the boiler in the form of hot water and steam. the entire heating output of the boiler in the form of hot water and steam.

  • Closed solar heating systems according to DIN 4757-1 and 2 with flow temperatures up to 120°C for all static heights.
  • District heating substations, house substations and house systems for connection to heating water district heating networks to DIN 4747-1 and AGFW 505.

Safety valves are permanently set and sealed at the factory.

TUV-Germany

Approvals

TÜV . SV . 22 - 665:

Usage

Steam/Gases (S/G)

Heating (H)

EU type examination

Approvals

01 202 642/B-18 T023 Rev.2:

Usage

Steam/Gases (S/G)

Heating (H)

Manufacture License of Special Equipment People's Republic of China

Approvals

TSF700E45-2023:

Usage

Steam/Gases (S/G)

Heating (H)

Eurasian Conformity

Approvals

EAЭC N RU Д-DE.CП28.B.08409/20:

EAЭC N RU Д-DE.CП28.B.00821/20:

Usage

Steam/Gases (S/G)

Heating (H)

Det Norske Veritas

Approvals

TAP00001W5:

Usage

Steam/Gases (S/G)

Lloyd's Register

Approvals

LR2089493TA:

Usage

Steam/Gases (S/G)

American Bureau of Shipping

Approvals

17-HG1633821-PDA:

Usage

Steam/Gases (S/G)

Bureau Veritas

Approvals

26401/C0 BV:

Usage

Steam/Gases (S/G)

Russian Maritime Register of Shipping

Approvals

19.40075.250:

Usage

Steam/Gases (S/G)